EN 54-16 Fire detection and fire alarm systems – Part 16: Voice alarm control and indicating equipment

Contents Page
Foreword 4
Introduction 6
1 Scope 7
2 Normative references 7
3 Terms, definitions and abbreviations 8
3.1 Terms and definitions 8
3.2 Abbreviations 10
4 General requirements 11
4.1 General 11
4.2 Combined VACIE and CIE 11
4.3 Power supply 11
5 General requirements for indications 11
5.1 Display and functional conditions 11
5.2 Indication display 12
5.3 Indication on alphanumeric displays 12
5.4 Indication of the supply of power 12
5.5 Additional indications 12
6 The quiescent condition 12
7 The voice alarm condition 12
7.1 Reception and processing of fire signals 12
7.2 Indication of the voice alarm condition 13
7.3 Audible warning (option with requirements) 13
7.4 Delays to entering the voice alarm condition (option with requirements) 13
7.5 Phased evacuation (option with requirements) 13
7.6 Silencing of the voice alarm condition 13
7.7 Reset of the voice alarm condition 14
7.8 Output to fire alarm devices (option with requirements) 14
7.9 Voice alarm condition output (option with requirements) 14
8 Fault warning condition 14
8.1 Reception and processing of fault signals 14
8.2 Indication of faults in specified functions 15
8.3 Indication of faults related to the transmission path to the CIE (option with requirements) 16
8.4 Indication of faults related to voice alarm zones (option with requirements) 16
8.5 System fault 16
8.6 Audible indication 16
8.7 Reset of fault indications 16
8.8 Transmission of the fault warning condition 16
9 Disablement condition (option with requirements) 17
9.1 General requirements 17
9.2 Indication of the disabled condition 17
9.3 Indication of specific disablements 17
9.4 Disablements and their indication 17
9.5 Transmission of the disablement condition 17
10 Voice alarm manual control (option with requirements) 18
10.1 General requirements 18
10.2 Indication of the voice alarm zones in an activated condition 18
10.3 Indication of the voice alarm zones in fault condition 18 10.4 Indication of the voice alarm zones in disablement condition 18
11 Interface to external control device(s) (option with the requirements) 18
12 Emergency microphone(s) (option with requirements) 19
13 Design requirements 19
13.1 General requirements and manufacturer’s declaration 19
13.2 Documentation 20
13.3 Mechanical design requirements 20
13.4 Electrical and other design requirements 21
13.5 Integrity of transmission paths 21
13.6 Accessibility of indications and controls 21
13.7 Indications by means of light emitting indicators 22
13.8 Indications on alphanumeric displays 22
13.9 Indication colours 22
13.10 Audible indications 23
13.11 Indicator testing 23
13.12 Audio performance 23
13.13 Message store(s) 25
13.14 Redundant power amplifiers (option with requirements) 25
14 Additional design requirements for software controlled VACIE 25
14.1 General requirements and manufacturer’s declarations 25
14.2 Software documentation 25
14.3 Software design 26
14.4 Program monitoring (see also Annex C) 26
14.5 The storage of programs and data (see also Annex C) 27
14.6 Monitoring of memory contents 27
15 Marking 27
16 Tests 28
16.1 General 28
16.2 Functional tests 29
16.3 Audio performance and environmental tests 31
16.4 Output power 32
16.5 Signal-to-noise ratio 34
16.6 Frequency response of VACIE without microphone(s) 35
16.7 Frequency response of VACIE with microphone(s) 36
16.8 Cold (operational) 37
16.9 Damp heat, steady state (operational) 38
16.10 Damp heat, steady state (endurance) 39
16.11 Impact (operational) 40
16.12 Vibration, sinusoidal (operational) 41
16.13 Vibration, sinusoidal (endurance) 42
16.14 Supply voltage variation (operational) 42
16.15 Electromagnetic Compatibility (EMC), Immunity tests (operational) 43
Annex A (informative) Explanation of access level 45
Annex B (informative) Optional functions with requirements and alternatives 47
Annex C (informative) Design requirements for software controlled VACIE 49
Annex D (informative) General information about voice alarm systems 50
Annex E (informative) Interface between the VACIE and the CIE 53
Annex F (informative) Common indications, controls and outputs when the VACIE and the CIE
are combined 54
Annex ZA (informative) Clauses of this European Standard addressing the provisions of the EU
Construction Products Directive (89/106/EEC) 56
Bibliography 65
Foreword
This document (EN 54-16:2008) has been prepared by Technical Committee CEN/TC 72 “Fire detection and fire alarm systems”, the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by September 2008, and conflicting national standards shall be withdrawn at the latest by March 2011.
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights.
This document has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association, and supports essential requirements of EU Directive(s).
For relationship with EU Directive, see informative Annex ZA, which is an integral part of this document.
EN 54 Fire detection and fire alarm systems consists of the following parts:
— Part 1: Introduction
— Part 2: Control and indicating equipment
— Part 3: Fire alarm devices – Sounders
— Part 4: Power supply equipment
— Part 5: Heat detectors – Point detectors
— Part 7: Smoke detectors – Point detectors using scattered light, transmitted light or ionization
— Part 10: Flame detectors – Point detectors
— Part 11: Manual call points
— Part 12: Smoke detectors – Line detectors using an optical light beam
— Part 13: Compatibility assessment of system components
— Part 14: Guidelines for planning, design, installation, commissioning, use and maintenance
— Part 15: Point detectors using a combination of detected phenomena
— Part 16: Voice alarm control and indicating equipment
— Part 17: Short-circuit isolators
— Part 18: Input/output devices
— Part 20: Aspirating smoke detectors
— Part 21: Alarm transmission and fault warning routine equipment
— Part 22: Line-type heat detectors
— Part 23: Fire alarm devices – Visual alarms
— Part 24: Components of voice alarm systems – Loudspeakers
— Part 25: Components using radio links
— Part 26: Point fire detectors using carbon monoxide sensors1)
— Part 27: Duct smoke detectors
1 Scope
This European Standard specifies requirements, methods of test and performance criteria for voice alarm control and indicating equipment for use in fire detection and fire alarm systems installed in buildings, where the alarm signal is in the form of tone(s) or voice message(s), or both.
It also provides for the evaluation of conformity of the equipment to the requirements of this European Standard.
NOTE The overall requirements of a voice alarm system, especially concerning audibility and intelligibility, are not covered in this part of EN 54. The manufacturer should consider requirements of an overall system that may affect the equipment design. Such system requirements may be specified in another part of EN 54, in national legislation, codes and standards or in contractual documents.
2 Normative references
The following referenced documents are indispensable for the application of this standard. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.
EN 54-1:1996, Fire detection and fire alarm systems — Part 1: Introduction
EN 54-2:1997, Fire detection and fire alarm systems — Part 2: Control and indicating equipment EN 54-2:1997/A1:2006, Fire detection and fire alarm systems — Part 2: Control and indicating equipment
EN 54-4:1997, Fire detection and fire alarm systems — Part 4: Power supply equipment EN 54-4:1997/A1:2002, Fire detection and fire alarm systems — Part 4: Power supply equipment EN 54-4:1997/A2:2006, Fire detection and fire alarm systems — Part 4: Power supply equipment
EN 50130-4:1995, Alarm systems — Part 4: Electromagnetic compatibility — Product family standard: Immunity requirements for components of fire, intruder and social alarm systems
EN 50130-4:1995/A1:1998, Alarm systems — Part 4: Electromagnetic compatibility — Product family standard: immunity requirements for components of fire, intruder and social alarm systems EN 50130-4:1995/A2:2003, Alarm systems — Part 4: Electromagnetic compatibility — Product family standard: immunity requirements for components of fire, intruder and social alarm systems
EN 60068-1:1994, Environmental testing — Part 1: General and guidance (IEC 60068-1:1988 + Corrigendum 1988 + A1:1992)
EN 60068-2-1:2007, Environmental testing — Part 2-1: Tests — Test A: Cold (IEC 60068-2-1:2007)
EN 60068-2-6:1995, Environmental testing — Part 2-6: Tests — Test Fc: Vibration (sinusoidal) (IEC 60068-2-6:1995 + Corrigendum 1995)
EN 60068-2-47:2005, Environmental testing — Part 2-47: Tests — Mounting of specimens for vibration, impact and similar dynamic tests (IEC 60068-2-47:2005)
EN 60068-2-75:1997, Environmental testing — Part 2-75: Tests — Test Eh: Hammer tests (IEC 60068-2-75:1997)
EN 60068-2-78:2001, Environmental testing — Part 2-78: Tests — Test Cab: Damp heat, steady state (IEC 60068-2-78:2001)
EN 60268-4:2004, Sound system equipment — Part 4: Microphones (IEC 60268-4:2004)
EN 60529:1991, Degrees of protection provided by enclosures (IP code) (IEC 60529:1989) EN 60529:1991/A1:2000, Degrees of protection provided by enclosures (IP code) – Amendment A1 (IEC 60529:1989/A1:1999)
EN 60721-3-3:1995, Classification of environmental conditions — Part 3: Classification of groups of environmental parameters and their severities — Section 3: Stationary use at wheatherprotected locations (IEC 60721-3-3:1994)
EN 60721-3-3:1995/A2:1997, Classification of environmental conditions — Part 3: Classification of groups of environmental parameters and their severities — Section 3: Stationary use at wheatherprotected locations – Amendment A2 (IEC 60721-3-3:1994/A2:1996)
EN ISO 9001:2000, Quality management systems — Requirements (ISO 9001:2000) IEC 60268-1, Sound system equipment — Part 1: General
3 Terms, definitions and abbreviations 3.1 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 54-1:1996 and the following apply.
3.1.1
access level
one of several states of a VACIE in which selected:
3.1.2
alphanumeric display
indicator that is capable of giving information by displaying messages consisting of text and/or numeric characters
3.1.3 cabinet
housing which affords the degree of protection and robustness required by this standard to its constituent parts and sub-assemblies (see 13.3)
3.1.4
earth fault
unwanted connection between earth potential and any part of the VACIE, transmission paths to the VACIE, or transmission paths between parts of the VACIE
3.1.5
emergency microphone
3.1.6
emergency microphone control
manual,control which activates an emergency microphone
NOTE Often called a “push to talk” control (PTT).
3.1.7 field
sub-division of a window of an alphanumeric display
3.1.8
functional condition
condition of the VACIE characterized by its indication at the VACIE
3.1.9 indicator
device which can change its state to give information
3.1.10 mandatory
adjective used to describe:
3.1.11
non-volatile memory
memory elements that do not require the presence of an energy source for the retention of their contents
3.1.12 octave
frequency band as defined in EN 61260
3.1.13
output power
maximum squared RMS output voltage divided by the minimum load resistance that can be maintained for a 1 kHz sinusoidal signal of specified duration, for a specified THD
3.1.14 program
software necessary for a VACIE to comply with at least the requirements of this European Standard, including initialising data, reset and interrupt vectors, operating code and variables
3.1.15 reset
operation capable of terminating the voice alarm condition and/or the fault warning condition
3.1.16
running data
alterable data subject to temporary modification during operation, either automatically or by manual controls
3.1.17 silencing
switching off an audible signal of a sounding device that is capable of being re-sounded by a new event
3.1.18
site specific data
alterable data required for the VACIE to operate in a defined system configuration
3.1.19
voice alarm transmission path
physical connection, external to the cabinet of the VACIE, for the transmission of information and/or power between parts of a VACIE contained in different cabinets and between the VACIE and other components of a voice alarm system, as defined in EN 54-1
3.1.20
voice alarm condition
when any fire alarm signal, recorded or live, is broadcast in at least one voice alarm zone
3.1.21
voice alarm output control
manual control which can be used to cause a voice alarm zone or group of voice alarm zones to sound an audible voice alarm signal
3.1.22
voice alarm control and indicating equipment
component of a voice alarm system that generates and transmits voice alarm signals to loudspeaker circuit(s) when it receives alarm signal(s) from a fire detection and alarm system and/or manual controls
3.1.23
voice alarm signal
audible fire alarm signal within the building, comprising a tone and/or a voice message
3.1.24
voice alarm zone
distinct geographic area containing a group of voice alarm loudspeakers intended to give the same voice alarm signal
3.1.25
volatile memory
memory elements that require the presence of an energy source for the retention of their contents
3.1.26 window
area of the alphanumeric display used for information relating to one functional condition at a given time 3.2 General requirements
4.1 General
4.1.1 If an optional function with requirements is included in the VACIE, then all the corresponding requirements shall be met. Annex B gives an overview of these optional functions with requirements.
4.1.2 If functions other than those specified in this European Standard are provided for the VACIE, they shall not jeopardize compliance with any requirements of this European Standard.
4.2 Combined VACIE and CIE
When the VACIE and CIE are combined they may share common indications, manual controls and outputs (see Annex F). In this case, the following shall apply:
a) a single fault in the CIE shall not adversely affect the mandatory functions of the VACIE;
b) indication(s) and manual control(s) of the voice alarm condition shall be clearly identifiable, with the exception of the optional audible warning.
4.3 Power supply
Power supply equipment, external or included in the VACIE, shall comply with the requirements of EN 54-4.
NOTE The power supply may be shared with that of the fire detection and fire alarm system.
5 General requirements for indications 5.1 Display and functional conditions
5.1.1 The VACIE shall be capable of unambiguously indicating the following functional conditions, as described in
5.1.2 The VACIE shall be capable of being simultaneously in any combination of the following functional conditions on different voice alarm zones:
All mandatory indications shall be clearly identifiable, except where otherwise specified in this European Standard.
5.2 Indication on alphanumeric displays
Where an alphanumeric display is used to display indications relating to different functional conditions these may be displayed at the same time. However, for each functional condition there shall be only one window, in which all of the information relating to that functional condition is grouped.
5.3 Indication of the supply of power
5.4.1 A visible indication shall be given by means of a separate discrete light emitting indicator while the VACIE is supplied with power.
5.4.2 Where the VACIE is distributed in more than one cabinet, an indication of supply of power to the cabinet shall be given on each distributed cabinet.
5.4 Additional indications
Where additional indications are provided, they shall be clearly identifiable and shall not override the primary indication of the VACIE.
6 The quiescent condition
Any kind of system information may be displayed during the quiescent condition. However, no indications shall be given which could be confused with indications used in:
7 The voice alarm condition
7.1 Reception and processing of fire signals
7.1.1 The VACIE shall be capable of receiving and processing alarm signals from the CIE or from manual control on the VACIE or both, and causing the appropriate voice alarm outputs to be activated within 3 s or on expiry of any delay period (see 7.4).
7.1.2 The mandatory indications and/or outputs shall not be falsified by multiple alarm signals received simultaneously from the CIE and/or manual controls.
7.1.3 Where the VACIE and CIE are in separate cabinets, failure of the transmission path between the CIE and the VACIE shall not result in any loss of control or any change of state of the VACIE, unless option 8.3 is used.
7.2 Indication of the voice alarm condition
7.2.1 The presence of a voice alarm condition shall be indicated on the VACIE, without prior manual intervention, by:
7.2.2 The audible warning shall be capable of being silenced at access level 1 or 2.
7.3 Audible warning (option with requirements)
The audible warning of the voice alarm condition (see 7.2.1 c)) may be the same as that for the fault warning condition. If they are different, the voice alarm condition warning shall have priority.
7.4 Delays to entering the voice alarm condition (option with requirements)
The VACIE may be provided with a facility to introduce a delay before entering the voice alarm condition. In this case:
a) the operation of the delay shall be selectable at access level 3;
b) the operation of the delay shall be in increments not exceeding 1 min up to a maximum of 10 min;
c) the delay to one output signal shall not affect the delay to other outputs;
d) it shall be possible to override the delay by a manual operation at access level 1;
e) there shall be provision to switch on and switch off delays by means of a manual operation at access level 2 (see Annex A for information on access levels);
f) there may be provision to automatically switch on and/or switch off delays by means of a programmable timer which shall be configurable at access level 3;
g) a separate discrete light emitting indicator and/or a field on the alphanumeric display shall be visible when a fire signal is received and the delay activated. This indication shall be suppressed when the VACIE enters the voice alarm condition.
7.5 Phased evacuation (option with requirements)
The VACIE may have a provision to phase the warning signals to the emergency loudspeaker zones. The facility shall be configurable at access level 3. There may be provision to switch on and switch off the phased evacuation sequence by means of a manual operation at access level 2 (see Annex A for information on access levels).
7.6 Silencing of the voice alarm condition
7.6.1 Silencing of the voice alarm condition from the CIE
7.6.1.1 Where the voice alarm condition has been triggered from the CIE, the VACIE shall respond appropriately to a silence instruction from the CIE.
7.6.1.2 The silencing procedure may allow for the completion of messages in the process of being broadcast.
7.6.2 Manual silencing of the voice alarm condition (option with requirements)
It may be possible to manually silence the voice alarm message from the VACIE at access level 2. In this case, following manual silencing, it shall be possible to re-activate the voice alarm message at access level 2.
7.7 Reset of the voice alarm condition
7.7.1 Reset of the voice alarm condition from the CIE
Where the voice alarm condition has been triggered from the CIE, the VACIE shall respond appropriately to a reset instruction from the CIE.
7.7.2 Manual reset of the voice alarm condition (option with requirements)
7.7.2.1 It may be possible to reset the voice alarm condition from the VACIE at access level 2 by means of a separate manual control. In this case, this control shall be used only for reset and may be the same as that used for reset from the fault warning condition.
7.7.2.2 Following a manual reset operation, the indication of the correct functional condition corresponding to any received signals shall either remain or be re-established within 20 s.
7.8 Output to fire alarm devices (option with requirements)
In addition to the voice alarm outputs the VACIE may have provision for the automatic transmission of fire alarm signals to fire alarm devices such as beacons and vibrating devices. In this case, the following shall apply:
a) it shall be possible to de-activate the fire alarm devices at access level 2;
b) following de-activation, it shall be possible to re-activate the fire alarm devices at access level 2;
c) the fire alarm devices shall not be de-activated automatically;
d) it shall be possible to configure the VACIE at access level 3 to automatically reactivate the fire alarm devices if an alarm is reported in an other zone.
7.9 Voice alarm condition output (option with requirements)
The VACIE may have provision for transmitting a signal that it is in the voice alarm condition. In this case, it shall activate the output only in the voice alarm condition.
8 Fault warning condition
8.1 Reception and processing of fault signals
8.1.1 The VACIE shall enter the fault warning condition when signals are received which, after any necessary processing, are interpreted as a fault.
8.1.2 The VACIE shall be capable of simultaneously recognizing all of the faults specified in 8.2 and, if provided, in 8.3 unless this is prevented by:
— the presence of an alarm output signal in the same voice alarm zone and/or
— the disablement of the corresponding voice alarm zone or function.
8.1.3 The VACIE shall enter the fault warning condition within 100 s of the occurrence of the fault, or the reception of a fault signal or within another time as specified in this European Standard or in other parts of EN 54.
8.2 Indication of faults in specified functions
8.2.1 The presence of faults in specified functions shall be indicated on the VACIE without prior manual intervention. The fault warning condition is established when the following are present:
8.2.2 If the indication is on an alphanumeric display, which cannot simultaneously indicate all of the faults because of its limited capacity, at least the following shall apply:
8.2.3 The following faults shall be indicated by means of separate light emitting indicators and/or an alphanumeric display:
8.2.4 The following faults shall be indicated at least by means of the general fault warning indicator:
8.3 Indication of faults related to the transmission path to the CIE (option with requirements)
The VACIE may have provision for an indication of faults related to the voice alarm transmission path to the CIE. In this case, the short circuit or interruption of the transmission path to the CIE shall be indicated by means of a separate light emitting indicator and/or an alphanumeric display.
8.4 Indication of faults related to voice alarm zones (option with requirements)
The VACIE may have provision for an indication of faults related to voice alarm zones. In this case the short circuit or interruption of a voice alarm transmission path between the VACIE and the loudspeakers in that zone shall be indicated by means of a separate light emitting indicator per zone and/or an alphanumeric display.
8.5 System fault
A system fault is a fault as specified in 14.4 or 14.6 in the case of software controlled VACIE. A system fault may prevent requirements of this European Standard, other than those specified below, from being fulfilled. In the event of a system fault at least the following shall apply:
8.6 Audible indication
8.6.1 The audible indication of faults required in 8.2 shall be capable of being silenced manually at access level 1 or 2 at the VACIE. The same manual operation may be used as for silencing the voice alarm condition.
8.6.2 The audible indication of faults shall be silenced automatically if the VACIE is automatically reset from the fault warning condition.
8.6.3 If previously silenced, the audible indication shall resound for each newly recognised fault.
8.7 Reset of fault indications
8.7.1 The indications of faults as required in 8.2 shall be capable of being reset:
a) automatically when faults are no longer recognised and/or
b) by a manual operation at access level 2.
8.7.2 Following reset as specified in 8.5.1, the indication of the correct functional conditions corresponding to any received signals shall either remain or be re-established within 20 s.
8.8 Transmission of the fault warning condition
The VACIE shall have provision for transmitting, by means of at least general fault signal, all faults specified in Clause 8. This fault signal shall also be given if the VACIE is de-energized.
9 Disablement condition (option with requirements)
9.1 General requirements
9.1.1 Disablements of the VACIE in accordance with the requirements of 9.4 shall inhibit all corresponding mandatory indications and/or outputs but shall not prevent other mandatory indications and/or outputs.
9.1.2 The VACIE shall have provision to independently disable and re-enable the function specified in 9.4 by means of manual operations at access level 2.
9.1.3 The VACIE shall be in the disabled condition while a disablement in accordance with the requirements of 9.4 exists.
9.1.4 Disablement and re-enablement shall not be affected by a reset from the voice alarm condition or from the fault warning condition.
9.2 Indication of the disabled condition
The disabled condition shall be indicated visibly, by means of:
a) a separate light emitting indicator (the general disablement indicator) and
b) an indication for each disablement, as specified in 9.3 and 9.4.
9.3 Indication of specific disablements
9.3.1 Disablements shall either be indicated within 2 s of the completion of the manual operation or, where a disablement cannot be completed within 2 s, it shall be indicated within 2 s that the disabling process is running.
9.3.2 The same light emitting indicator may be used as that for the indication of the corresponding fault, although the indication shall be distinguishable.
9.3.3 If the indication is on an alphanumeric display, which cannot simultaneously indicate all of the disablements because of its limited capacity, at least the following shall apply:
9.4 Disablements and their indication
Voice alarm zones may be capable of being independently disabled and re-enabled. In this case the disablements shall be indicated by means of separate light emitting indicators per zone and/or an alphanumeric display. The indications shall not be suppressed during the voice alarm condition.
9.5 Transmission of the disablement condition
The VACIE shall have provision for transmitting, by means of a general disablement signal, all disablement conditions specified in this clause.
10 Voice alarm manual control (option with requirements)
10.1 General requirements
The VACIE may have provision for manually activating the voice alarm condition. If a voice alarm manual control is provided the following shall apply:
10.2 Indication of the voice alarm zones in an activated condition
The indication for the voice alarm condition in the voice alarm zone(s) associated with each manual control shall be available without any manual action and shall not be suppressed. This indication shall be by means of:
10.3 Indication of the voice alarm zones in fault condition
The indication for the fault condition of the VACIE, which would prevent the generation and transmission of the voice alarm signal to the voice alarm zone(s) associated with each manual control, shall be available without any manual action and shall not be suppressed. This indication shall be by:
10.4 Indication of the voice alarm zones in disablement condition
The indication for the disablement condition in the voice alarm zone(s) associated with each manual control shall be available without any manual action and shall not be suppressed. This indication shall be by:
NOTE The external control devices should comply with available local codes, European Standards or national standards.
12 Emergency microphone(s) (option with requirements)
The VACIE may have provision for emergency microphone(s). In this case the emergency microphone(s) shall
have:
13 Design requirements
13.1 General requirements and manufacturer’s declaration ^
13.1.1 The VACIE shall comply with the design requirements of this clause, where relevant to the technology used. Some requirements can be verified by testing. Others can only be verified by inspection of the design :’ and its accompanying documentation because of the impracticability of testing all of the possible combinations of functions and of establishing the long-term reliability of the VACIE.
13.1.2 In order to assist the process of design inspection, the manufacturer shall declare the following in ‘ writing:
a) that the design has been carried out in accordance with a quality management system which incorporates a set of rules for the design of all elements of the VACIE and
b) that the components of the VACIE have been selected for the intended purpose and are expected to operate within their specifications when the environmental conditions outside the cabinet of the VACIE comply with Class 3k5 of EN 60721-3-3:1995 as amended by EN 60721-3-3:1995/A2:1997.
13.2 Documentation
13.2.1 The manufacturer shall prepare installation and user documentation which shall be submitted for assessment together with the VACIE. This shall comprise at least the following:
13.2.2 The manufacturer shall prepare design documentation that shall be submitted for assessment together with the VACIE. This documentation shall include drawings, parts lists, block diagrams, circuit diagrams and a functional description to such an extent that compliance with this European Standard may be checked and that a general assessment of the mechanical and electrical design is made possible.
13.3 Mechanical design requirements
13.3.1 The cabinet of the VACIE shall be of robust construction consistent with the method of installation recommended in the documentation. It shall meet at least classification IP30 of EN 60529:1991 as amended by EN 60529:1991/A1:2000.
13.3.2 All interconnections and settings inside the cabinet shall be accessible at level 3.
13.3.3 The VACIE may be housed in more than one cabinet. If the documentation shows that the cabinets may be installed in locations distributed within the protected premises, then all of the mandatory manual controls and indicators shall be on one cabinet or on cabinets declared to be only suitable for mounting adjacent to each other.
13.3.4 All mandatory manual controls and light emitting indicators shall be clearly labelled to indicate their purpose. The labels shall be legible at 0,8 m distance in an ambient light intensity from 100 lux to 500 lux.
13.3.5 The terminations for transmission paths and the fuses shall be clearly labelled.
13.4 Electrical and other design requirements
13.4.1 The processing of signals shall give the highest priority to the voice alarm condition.
13.4.2 Transitions between the main and the standby power sources shall not change any indications and/or the state of any outputs, except those relating to the power supplies.
13.4.3 If the VACIE have provision for disconnecting or adjusting the main or the standby power source, this shall only be possible at access level 3 or 4.
13.5 Integrity of transmission paths
13.5.1 A fault in any voice alarm transmission path between the VACIE and other components of the voice alarm system shall not affect the correct functioning of the VACIE or of any other voice alarm transmission path.
13.5.2 A short circuit or an interruption in the transmission path to the loudspeaker(s) shall not affect more than one voice alarm zone for longer than 100 s following the occurrence of the fault.
13.5.3 A single short circuit or an interruption in any voice alarm transmission path between distributed cabinets of a VACIE shall not prevent the activation of a voice alarm output condition to more than one voice alarm zone for longer than 100 s following the occurrence of the fault.
13.5.4 If the VACIE is designed to be used with a power supply (item L of Figure 1 of EN 54-1:1996) contained in a separate cabinet, then an interface shall be provided for at least two voice alarm transmission paths to the power supply, such that a short circuit or an interruption in one does not affect the other.
13.6 Accessibility of indications and controls
Four access levels, as described in Annex A, shall be provided on the VACIE, from access level 1 (most accessible) to access level 4 (i.e. least accessible). Manual controls at a given access level shall not be accessible at a lower access level. The following shall apply:
13.7 Indications by means of light emitting indicators
13.7.1 Mandatory indications from light emitting indicators shall be visible in an ambient light intensity up to 500 lux, at any angle up to 22,5° from a line through the indicator perpendicular to its mounting surface:
13.7.2 If flashing indications are used, both the on period and the off period shall be greater than or equal to 0,25 s, and the frequencies of flash shall not be less than:
13.7.3 If the same light emitting indicators are used for the indication of specific faults and disablements, fault indications shall be flashing and disablement indications shall be steady.
13.8 Indications on alphanumeric displays
13.8.1 If an alphanumeric display consists of elements or segments, the failure of one of these shall not affect the interpretation of the displayed information.
13.8.2 If an alphanumeric display is used to display mandatory indications, it shall be clear and unambiguous.
13.8.3 Mandatory indications on an alphanumeric display shall be legible for at least one hour following the display of a new indication of the voice alarm condition and at least 5 min for fault or disablement conditions, at 0,8 m distance, in ambient light intensities from 5 lux to 500 lux, at any angle from the normal to the plane of the display up to:
13.9 Indication colours
13.9.1 The colours of the general and specific indications from light emitting indicators shall be:
13.9.2 The use of different colours is not necessary for indications on alphanumeric displays. However, if different colours are used for different indications, the colours used shall be as specified in 13.9.1.
13.10 Audible indications
13.10.1 Audible indicators shall be part of the VACIE. The same device may be used for voice alarm zone activated and fault warning indications.
13.10.2 The minimum sound pressure level, measured under anechoic conditions at a distance of 1 m, with any access door(s) on the VACIE closed, shall be:
13.11 Indicator testing
All mandatory visible and audible indicators shall be testable by a manual operation at access level 1 or 2.
13.12 Audio performance
13.12.1 Output power
The VACIE output power shall be as declared by the manufacturer.
13.12.2 Signal-to-noise ratio
The VACIE shall have an A-weighted signal-to-noise ratio of at least 45 dB according to IEC 60268-1.
13.12.3 Frequency response
The frequency response of the VACIE shall fit within the non-shaded area in Figure 1 — VACIE frequency response limits without microphone(s) for sound sources without microphone(s) (e.g. message store) and Figure 2 — VACIE frequency response limits with microphone(s) for sound sources with microphone(s).
13.13 Message store(s)
Pre-recorded messages shall be stored in non-volatile memory that retains the messages when all power sources are removed.
NOTE Tapes or magnetic or optical data disks for the storage of emergency messages are not considered suitable at the time of drafting this European Standard (see Annex C).
13.14 Redundant power amplifiers (option with requirements)
13.14.1 The VACIE may have provision for at least one spare power amplifier. In this case:
the spare power amplifier(s) shall have at least the same functionality and output power as the replaced amplifier.
13.14.2 Every fault of an amplifier shall be indicated by the general fault warning indicator as specified in 8.2.
13.14.3 Supervision of the spare amplifier(s) shall be maintained during the functional condition whilst the VACIE is powered by either the mains or standby power supplies.
14 Additional design requirements for software controlled VACIE
14.1 General requirements and manufacturer’s declarations
In order to fulfil requirements of this European Standard the VACIE may contain elements which are controlled by software. In this case, the VACIE shall comply with the requirements of Clause 14 as well as those of Clause 13, where relevant to the technology used.
14.2 Software documentation
14.2.1 The manufacturer shall prepare documentation that gives an overview of the software design, which shall be submitted for assessment together with the VACIE. This documentation shall be in sufficient detail for the design to be inspected for compliance with this European Standard and shall comprise at least the following:
Where dynamic memory management is employed, a separation shall be implemented between the program, site specific data and running data and this shall be described in connection with the method of memory allocation.
14.2.2 The manufacturer shall prepare and maintain detailed design software documentation. This need not be submitted for assessment but shall be available for inspection in a manner which respects the manufacturer’s rights of confidentiality. This documentation shall comprise at least the following:
14.3 Software design
In order to ensure the reliability of the VACIE the following requirements for software design shall apply:
a) the software shall have a modular structure;
b) the design of the interfaces for manually and automatically generated data shall not permit invalid data to cause an error in the program execution;
c) the software shall be designed to avoid the occurrence of a deadlock in the program flow.
14.4 Program monitoring (see also Annex C)
14.4.1 The execution of the software program shall be monitored as under 14.4.2 or 14.4.3. If routines associated with the main functions of the program are no longer executed, either or both of the following shall apply:
a) the VACIE shall indicate a system fault (as in 8.3);
b) the VACIE shall enter the fault warning condition and indicate faults of affected supervised functions (as in 8.2.3, 8.2.4, 8.3, 8.4, and 8.5), where only these functions are affected.
14.4.2: If the software program executes in one processor, the execution of the routines in 14.4.1, it shall be monitored by a monitoring device as in 14.4.4.
14.4.3 If the software program executes in more than one processor, the execution of the routines in 14.4.1 shall be monitored in each processor. A monitoring device as in 14.4.4 shall be associated with one or more processors, and at least one such processor shall monitor the functioning of any processor not associated with such a monitoring device.
14.4.4 The monitoring device of 14.4.2 and 14.4.3 shall have a time-base independent of that of the monitored system. The functioning of the monitoring device, and the signalling of a fault warning, shall not be prevented by a failure in the execution of the program of the monitored system.
14.4.5 In the event of a system fault as specified in 14.4.1 a) or 14.6, those parts of the VACIE affected shall enter a safe state not later than the indication of the system fault. This safe state shall not result in the false activation of mandatory outputs.
14.5 The storage of programs and data (see also Annex C)
14.5.1 All executable code and data necessary to comply with this European Standard shall be held in memory that is capable of continuous, un-maintained, reliable operation for a period of at least 10 years.
14.5.2 For each software program, the following requirements shall apply:
a) the program shall be held in non-volatile memory, which can only be written to at access level 4 and
b) it shall be possible to identify the version reference or references of the program at access level 3. The version reference or references shall be in accordance with the documentation of 14.2.1.
14.5.3 For site-specific data, including emergency message(s), the following requirements shall apply:
14.6 Monitoring of memory contents
The contents of the memories containing the site specific data shall be automatically checked at intervals not exceeding 1 h. The checking device shall signal a system fault if a corruption of the memory contents is detected.
15 Marking
The VACIE shall be marked with the following information, which shall be legible at access level 1:
a) the number of this European Standard, i.e. EN 54-16;
b) the name or trademark of the manufacturer or supplier;
c) the type number or other designation of the VACIE.
It shall be possible to identify a code or number that identifies the production period of the VACIE at access level 1 or 2 or 3.
16.1.1 Combined VACIE and CIE
When the VACIE is integrated within the CIE, the testing in accordance with this standard shall be combined with the testing in accordance with of EN 54-2. The functional test program of 16.2 of this standard shall be combined with the functional test program of 15.2 of EN 54-2:1997 as amended by EN 54-2:1997/A1:2006.
16.1.2 Standard atmospheric conditions for testing
Unless otherwise stated in a test procedure, the testing shall be carried out on the VACIE after the test specimen has been allowed to stabilize in the standard atmospheric conditions for testing as described in EN 60068-1:1994 as follows:
The temperature and humidity shall be substantially constant for each environmental test where the standard atmospheric conditions are applied.
16.1.3 Specimen configuration
The specimen configuration shall include at least one of each type of voice alarm function. When the VACIE is constructed from configurable functions or when these functions can be distributed in several cabinets, the exact test configuration shall be agreed between the test laboratory and the manufacturer.
16.1.4 Mounting and orientation of specimen
Unless otherwise stated in a test procedure, the specimen shall be mounted in its normal orientation by the normal means of mounting indicated by the manufacturer. The equipment shall be in the condition of access level 1, except where otherwise required for functional testing.
16.1.5 Electrical connection
If the test procedure requires the specimen to be in the operating condition, it shall be connected to a power supply complying with the requirements in EN 54-4.
Unless otherwise required the power supply shall be in the nominal operating condition.
All voice alarm output circuits and transmission paths shall be connected to cables and equipment or to dummy loads. At least one of each type of voice alarm output circuit shall be loaded to its maximum capacity within the manufacturer’s specification. Equipment other than the VACIE may be kept in the standard atmospheric condition during the tests.
16.1.6 Provision for tests
At least one VACIE specimen shall be provided for testing compliance with this European Standard.
The specimen(s) submitted shall be representative of the manufacturer’s normal production and shall include the claimed options.
16.2 Functional tests
16.2.1 Object of the tests
The object of the functional tests is to demonstrate the performance of the VACIE before, during and/or after the environmental conditioning.
16.2.2 Test schedule
16.2.2.1 General
A test schedule shall be drawn up which ensures that during the functional tests, each type of input function and each type of output function is exercised.
This shall include as a minimum tests of the voice alarm condition (input from the CIE of an alarm condition and, if provided, manual activation), the fault warning condition and the disabled condition.
16.2.2.2 Voice alarm condition
Initiate, silence and reset a voice alarm condition to at least two voice alarm zones (unless only one zone is provided).
Check that the correct indications, outputs and functions, as specified in Clause 7, are given and/or executed.
16.2.2.3 Fault warning condition
Initiate and reset fault warnings corresponding at least to the following:
16.2.2.4 Disablement condition
When the disablement condition is provided as an option with requirements:
— disable and restore one voice alarm zone;
— check that the correct indications, outputs and functions, as specified in Clause 9, are given and/or executed.
16.2.2.5 Voice alarm manual control
When the voice alarm manual control is provided as an option with requirements:
16.2.2.6 Interface to external control device(s)
When an interface to external control device(s) is (are) provided as an option with requirements:
16.2.2.7 Emergency microphone(s)
When emergency microphone(s) is/are provided as an option with requirements:
16.2.2.8 Microphone priority
When the option of microphone priority is provided, check the requirements as specified in Clause 12.
16.2.2.9 Redundant power amplifiers
When redundant power amplifiers are provided as an option with requirements, check the requirements as specified in 13.14.
16.2.3 Requirements
During the tests required in 16.8, 16.9, 16.11, 16.12, 16.14 and 16.15 the specimens shall not change status in each of the functional conditions as specified in the corresponding clauses, except when such a change is required by the test procedure or when the change is a result of a functional test.
When subjected to the functional tests in 16.2.2 each specimen shall respond correctly. 16.3 Audio performance and environmental tests
16.3.1 General
One or several specimens (see 16.3.2 and 16.3.3) may be supplied for testing. The audio performance tests and operational and endurance tests to be applied are shown in Table 1 — Test schedule on VACIE.
16.3.2 Tests on one specimen
If a single specimen is supplied for environmental testing, the specimen shall be subjected to all the tests, which may be carried out in any order. A functional test shall be carried out on the specimen before and after each environmental test. For each specimen, the functional test after one environmental test may be taken as the functional test before the next environmental test.
16.3.3 Tests on two or more specimens
If more than one specimen is supplied for environmental testing, then tests may be divided between the specimens and carried out in any order. A functional test on the specimen before and after each environmental test shall be carried out. For each specimen, the functional test after one environmental test may be taken as the functional test before the next environmental test.
16.4.1 Object of the test
To check that the VACIE output power is not less than the rating declared by the manufacturer.
16.4.2 Test procedure 16.4.2.1 General
The following components shall be included in the measurement:
Mount the specimen as specified in 16.1.4 and connect it to suitable power supply, monitoring and loading equipment as specified in 16.1.5.
16.4.2.2 Conditioning
The following severity of conditioning shall be applied:
— temperature: (40 ± 2) °C.
Precondition the specimen at the conditioning temperature (40 ± 2) °C until temperature stability has been reached to prevent the formation of water droplets on the specimen.
Terminate the VACIE output(s) with the minimum resistive and maximum capacitive load as specified by the manufacturer.
Adjust the power supply equipment output to the minimum voltage as specified by the manufacturer.
Apply the 1 kHz sinusoidal signal to the input of the specimen and adjust the gain of the system until the rated RMS output power is achieved.
Maintain this gain for 1 min.
16.4.2.3 Measurement during conditioning
The following shall be measured:
a) the THD of the VACIE output signal(s) during the conditioning and
b) the RMS voltage of the sinusoidal signal at the beginning and end of the conditioning (16.4.2.3).
16.4.2.4 Final measurements
Measure the frequency response of the specimen in accordance with 16.6 and/or 16.7, as applicable. 16.4.3 Test requirements
The specimen shall be deemed to meet the requirements of this test if:
aGeneral
The following components shall be included in the measurement:
— the minimum resistive and maximum capacitive load, as specified by the VACIE manufacturer, representing the loudspeaker lines and loudspeakers connected to the specimen to at least two emergency loudspeaker zones (unless only one zone is provided);
— a 1 kHz sinusoidal signal generator;
— equipment required to measure the RMS output voltage level, with and without A-weighting (see IEC 60268-1);
— any other equipment used during the operation of the VACIE.
16.5.2.1 State of the specimen during conditioning
The specimen shall be mounted as specified in 16.1.4 and shall be connected to suitable power supply, monitoring and loading equipment as specified in 16.1.5.
The specimen shall be in the quiescent condition.
16.5.2.2 Conditioning
The output of the power supply equipment shall be adjusted to the minimum voltage specified by the manufacturer of the VACIE.
The following signals shall be applied to the specimen:
a) 1 kHz sinusoidal signal such that the rated output power is measured at the output of the specimen (as measured in 16.4.2.4 a)), immediately followed by;
b) no signal, with the inputs terminated with a load equivalent to the equipment design requirement.
16.5.2.3 Measurement during conditioning
Measure the A-weighted RMS voltage of the output noise level.
— the specimen to be tested;
— the minimum resistive and maximum capacitive load, as specified by the VACIE manufacturer, representing the loudspeaker lines and loudspeakers connected to the VACIE to at least two emergency loudspeaker zones (unless only one zone is provided);
— a sinusoidal signal generator;
— equipment required to perform the frequency response measurement (see 11.1 of EN 60268-4:2004);
— any other equipment used during the operation of the VACIE.
16.6.2.1 State of the specimen during conditioning
The specimen shall be mounted as specified in 16.1.4 and connected to suitable power supply monitoring and loading equipment as specified in 16.1.5.
Manual controls that influence frequency response such as bass, treble or other equalizers shall be adjusted to their flat response settings.
The specimen shall be in the quiescent condition.
16.6.2.2 Conditioning
In order to determine a reference input level for the frequency response measurement, generate a 1 kHz sinusoidal signal such that a level 10 dB below the measured output level as measured in 16.4.3) is achieved.
Apply a sinusoidal signal at this reference input level from 125 Hz to 20 kHz in steps of 1/3 octave to the input of the VACIE.
16.6.2.3 Measurements during conditioning
The RMS output value of the VACIE shall be measured for each specified frequency, f These levels shall be recorded as Lm fm).
16.6.3 Test requirements
The VACIE shall be deemed to comply with the requirement of this test if the frequency response curve obtained Lm fm) fits within the un-shaded area shown in Figure 1 — VACIE frequency response limits without microphone(s).
16.7 Frequency response of VACIE with microphone(s)
16.7.1 Object of the test
16.7.2.1 State of the specimen during conditioning
The specimen shall be mounted as specified in 16.1.4 and connect it to suitable power supply, monitoring and loading equipment as specified in 16.1.5.
Manual controls that influence frequency response such as bass, treble and other equalizers shall be adjusted as recommended by the manufacturer.
The specimen shall be in the quiescent condition.
The conditions as specified in EN 60268-4:2004, 11.1.2 shall be applied at the VACIE microphone with an angle of incidence of 0 degrees.
16.7.2.2 Conditioning
In order to determine an acoustical reference input level for the frequency response measurement, the system shall be calibrated with a 1 kHz sinusoidal acoustical signal with a sound pressure level of up to 104 dB. This sound pressure level shall be applied at the entrance of the VACIE microphone at an incidence of 0 degrees and the gain of the system shall be adjusted until an output level 10 dB below the output level measured in
16.4.2.4 a) is achieved.
NOTE When testing systems using a close-talking microphone, a sound pressure level of 104 dB is normally used. With all other types of microphone a sound pressure level of 94 dB is normally used.
Apply acoustical sinusoidal signals in the frequency range 200 Hz to 10,0 kHz in steps of 1/3 octaves to the VACIE microphone for a duration long enough to measure the RMS signal level at the output of the VACIE. For each frequency, the measurement system shall be corrected, such that the sound pressure level at the VACIE microphone does not deviate by more than +2/-3 dB from the calibrated 1 kHz signal at the entrance of the microphone.
16.7.2.4 Measurements during conditioning
The signal level at the output of the VACIE shall be measured at the 1/3 octave centre frequency for each of the sinusoidal signals applied to the VACIE microphone. These levels shall be measured as the average true RMS values over a period of at least 1 s as soon as a stable level can be measured.
NOTE This stabilizing process may take several seconds. 16.7.3 Test requirements
The VACIE shall be deemed to comply with the requirement of this test if the frequency response curve obtained fits within the un-shaded area in Figure 2 — VACIE frequency response limits with microphone(s).
16.8 Cold (operational)
16.8.1 Object of the test
To demonstrate the ability of the VACIE to function correctly at low ambient temperatures appropriate to the anticipated service environment.
16.8.2 Test procedure
16.8.2.1 General
The test procedures with gradual changes in temperature as specified in EN 60068-2-1:2007 shall be used. Test Ad shall be used for heat-dissipating specimens and Test Ab shall be used for non-heat-dissipating specimens.
16.8.2.2 Initial examination
Before conditioning, subject the specimen to the functional test.
16.8.2.3 State of the specimen during conditioning
Mount the specimen as specified in 16.1.4 and connect it to suitable power supply, monitoring and loading equipment as specified in 16.1.5.
The specimen shall be in the quiescent condition.
16.8.2.4 Measurements during conditioning
Monitor the specimen during the conditioning period to detect any change in status. During the last hour of the conditioning period, subject the specimen to the functional test.
16.8.2.5 Final measurements
After the recovery period, subject the specimen to the functional test schedule specified in 16.2 and inspect it visually for mechanical damage both externally and internally.
16.9 Damp heat, steady state (operational)
16.9.1 Object of the test
To demonstrate the ability of the VACIE to function correctly at high relative humidity (without condensation) which can occur for short periods in the service environment.
16.9.2 Test procedure
16.9.2.1 General
Use the test procedure described in EN 60068-2-78:2001.
16.9.2.2 Initial examination
Before conditioning, subject the specimen to the functional test.
16.9.2.3 State of the specimen during conditioning
Mount the specimen as specified in 16.1.4 and connect it to a suitable power supply, monitoring and loading equipment specified in 16.1.5.
The specimen shall be in the quiescent condition.
16.9.2.4 Conditioning
To demonstrate the ability of the VACIE to withstand the long-term effects of humidity in the service environment (e.g. changes in electrical properties due to absorption, chemical reactions involving moisture, galvanic corrosion).
16.10.1 Test procedure
16.10.2.1 General
Use the test procedure described in EN 60068-2-78:2001.
16.10.2.2 Initial examination
Before conditioning, subject the specimen to the functional test.
16.10.2.3 State of the specimen during conditioning
Mount the specimen as required in 16.1.4 and connect it to suitable power supply, monitoring and loading equipment specified in 16.1.5.
.
16.11 Impact (operational)
16.11.1 Object of the test
To demonstrate the immunity of the VACIE to mechanical impacts upon the surface, which it may sustain in the normal service environment and which it can reasonably be expected to withstand.
16.11.2 Test procedure
16.11.2.1 General
Apply the test apparatus and procedure described in EN 60068-2-75:1997, Test Eh.
16.11.2.2 Initial examination
Before conditioning, subject the specimen to the functional test.
16.11.2.3 State of the specimen during conditioning
Mount the specimen as specified in 16.1.4 and connect it to a suitable power supply, monitoring and loading equipment as specified in 16.1.5.
The specimen shall be in the quiescent condition.
16.11.2.4 Conditioning
Apply impacts to all surfaces of the specimen that are accessible at access level 1.
For all such surfaces three blows shall be applied to any point(s) considered likely to cause damage to or impair the operation of the specimen.
Care shall be taken to ensure that the results from a series of three blows do not influence subsequent series. In case of doubts, the defect shall be disregarded and a further three blows shall be applied to the same position on a new specimen.
Apply the following severity of conditioning:
— impact energy: (0,5 ± 0,04) J;
— number of impacts per point: 3.
16.11.2.5 Measurements during conditioning
Monitor the specimen during the conditioning periods to detect any changes in functional condition and to ensure that
NOTE The vibration operational test may be combined with the vibration endurance test, so that the specimen is subjected to the operational test conditioning followed by the endurance test conditioning in each axis.
16.12.2.1 Initial examination
Before conditioning, subject the specimen to the functional test.
16.12.2.2 State of the specimen during conditioning
Mount the specimen as specified in 16.1.4 and in accordance with the requirements of EN 60068-2-47:2005 and connect it to a suitable power supply, monitoring and loading equipment as specified in 16.1.5.
The specimen shall be tested in the quiescent condition.
16.12.2.3 Conditioning
16.12.2.4 Measurements during conditioning
Monitor the specimen during the conditioning period to detect any changes in functional conditions.
16.12.2.5 Final measurements
After the conditioning, subject the specimen to the functional test schedule specified in 16.2 and inspect it visually for mechanical damage both externally and internally.
16.13 Vibration, sinusoidal (endurance)
16.13.1 Object of the test
To demonstrate the ability of the VACIE to withstand the long-term effects of vibration at levels appropriate to the environment.
16.13.2 Test procedure
16.13.2.1 General
Use the test procedure described in EN 60068-2-6:1995.
NOTE The vibration endurance test may be combined with the vibration operational test, so that the specimen is subjected to the operational test conditioning followed by the endurance test conditioning in each axis in turn.
16.13.2.2 Initial examination
Before conditioning subject the specimen to the functional test.
16.13.2.3 State of the specimen during conditioning
Mount the specimen as require in 16.1.4 and in accordance with EN 60068-2-47:2005 and connect it to a suitable power supply, monitoring and loading equipment as specified in 16.1.5.
The specimen shall not be supplied with power during the conditioning.
After conditioning, subject the specimen to the functional test as specified in 16.2 and inspect it visually for mechanical damage both externally and internally.
16.14 Supply voltage variation (operational) 16.14.1 Object of the test
To demonstrate the ability of the VACIE to function correctly over the anticipated range of supply voltage conditions.
16.14.2 Test procedure
16.14.2.1 General
The specimen shall be subjected to each of the specified power supply conditions until temperature stability is reached and the functional test has been conducted.
16.14.2.2 Initial examination
Before conditioning, subject the specimen to the functional test.
16.14.2.3 State of the specimen during conditioning
Mount the specimen as specified in 16.1.4 and connect it to suitable power supply, monitoring and loading equipment as specified in 16.1.5.
The specimen shall be in the quiescent condition.
16.14.2.4 Conditioning
Apply the following conditions:
16.14.2.5 Measurements during conditioning
Monitor the specimen at the supply voltage conditions until temperature stability is reached and subject the specimen to the functional test at each voltage condition.
16.14.2.6 Final measurements
After the conditioning subject the specimen to the functional test.
16.15 Electromagnetic Compatibility (EMC), Immunity tests (operational)
16.15.1 The following EMC immunity tests shall be carried out on the VACIE, as described in EN 50130-4:1995 as amended by EN 50130-4:1995/A1:1998 and EN 50130-4:1995/A2:2003:
16.15.2 For the tests described in 16.15.1 a) to g), the criteria for compliance specified in EN 50130-4:1995
and the following shall apply:
A.1 Introduction
This standard defines access level (see 3.1.1 and 13.6) for the indications and controls relating to mandatory functions. In some cases alternatives are offered (e.g. access level 1 or 2). This is because either may be appropriate in different operational circumstances. The purpose of the different access levels is not defined by this European Standard. However, in general, they are expected to be used as described below.
A.2 Access levels
A.2.1 Access level 1 :
By member(s) of the general public or persons having a general responsibility for safety supervision who might be expected to investigate and initially respond to a fire alarm or a fault warning.
A.2.2 Access level 2
By persons having a specific responsibility for safety and who are trained and authorized to operate the VACIE in the:
— quiescent condition,
— voice alarm output condition,
By persons who are trained and authorized by the manufacturer to either repair the VACIE or alter its firmware, thereby changing its basic mode of operation.
The minimum requirements for accessibility are defined in 13.6. Only access levels 1 and 2 have a strict hierarchy. Examples of special procedures for entry to access level 2 and/or to access level 3 are the use of:
It may be acceptable that the entry to access level 4 requires only a simple tool, such as a screwdriver, after access level 2 or 3 has been reached. For example, the manufacturer may declare in his documentation which parts of the VACIE is not user serviceable, and the entry to access level 4 may then be controlled by management of the user. It is also considered acceptable to use external tools to carry out certain functions at access level 3, e.g. to program site-specific data.
A.2.6 Additional access levels
It may be desirable in certain circumstances that the VACIE has additional access levels within access level 2, or access level 3 (e.g. 2A and 2B), which would permit different classes of authorized user to have access to a selected group of controls or functions. This is not forbidden by this European Standard. The exact configuration will depend on the type of installation, the way the VACIE is used, and the complexity of the functions provided.
Optional functions with requirements and alternatives B.1 Optional functions with requirements
This European Standard specifies mandatory functions and options with requirements (see 4.1.1). A VACIE complying with this European Standard will need to fulfill the requirements of all of the mandatory functions, together with the requirements of those optional functions that are provided. The options described in this European Standard are currently used in the CEN member states and have been incorporated into this European Standard in order to comply with application guidelines. They may also be called up in national codes of practice. Optional functions of VACIE and their relevant clause numbers are listed in Table B.1.
B.2 Alternatives
In addition, alternatives are offered in this European Standard. Examples of these are:
— automatic or manual reset of the fault warning condition;
— indications by means of separate light emitting indicators or on an alphanumeric display;
— access level 1 or 2 for certain functions.
The choice of an alternative is entirely up to the manufacturer. These alternatives are equivalent solutions in this European Standard.
Design requirements for software controlled VACIE
C.1 The VACIE may incorporate software controlled elements, which are required to fulfil mandatory requirements of this European Standard (see Clause 14), but which are supplied to the manufacturer. A good example is an alphanumeric display module, but there are many possibilities including both physical modules and embedded software (e.g. operating systems). Such elements may be traded world-wide as commodity items, and detailed software documentation (and for that matter details of the hardware design) may not be available to the VACIE manufacturer. It is not the intention of this European Standard to forbid the use of appropriate technology and in such cases the detailed requirements for documentation and design of 14.2 and 14.3 may be relaxed, as long as sufficient information is provided to allow performance to be evaluated. However, it is expected that products from third parties which are designed and produced exclusively for a VACIE are fully documented and fulfil the requirements. The manufacturer has to ensure that the element is of proven reliability and is suitable for the application. Proven reliability can be assumed if the components under question are freely available on the market and there is sufficient field experience (e.g. > 1 year). The interface with the main application has to be clearly and comprehensively specified, and this documentation has to be available to the test laboratory.
C.2 14.4 deals with program monitoring. The program is the software necessary for the VACIE to carry out mandatory functions (including any declared options with requirements). The execution of the entire program has to be monitored. Monitoring can be carried out either by means of a hardware watchdog system or by another processor. The program may include software which runs in more than one processor and software in elements supplied to the manufacturer. The degree of monitoring should be sufficient to ensure that the VACIE is at least able to meet the requirements of this standard. In the case of an alphanumeric display module, it is considered to be sufficient to routinely check that data written to the module may be read back from it.
C.3 14.4.5 requires that, in the event of a failure of program execution, the VACIE shall enter a safe state. The safe state is defined by the manufacturer, but should not result in the false activation of mandatory outputs, nor give a false impression to a user that the VACIE remains operational if it is not. In practice, it may be acceptable either to stop, or automatically restart the program execution. If there is a possibility that memory may have been corrupted, the restart procedure should check the contents of this memory and if necessary, re-initialise the running data to ensure that the VACIE enters a safe operating state. Even if program execution is successfully restarted, it is important that the user is made aware of the incident. For this reason it may be advantageous for the VACIE to be capable of automatically recording details of the restart event. In any event the system fault indication has to be latched until a manual intervention.
C.4 14.5.1 requires that all executable code and data necessary to comply with this European Standard is held in memory which is capable of continuous, non-maintained, reliable operation for a period of at least 10 years. In the existing state of the art, memory with moving mechanical parts is not believed to be sufficiently reliable. For example; the use of tapes or, magnetic or optical data discs, for the storage of programs and data, therefore, is not considered suitable at the time of drafting this European Standard.
General information about voice alarm systems
D.1 General
A voice alarm system (see 3.1.22) that is connected to a fire detection and fire alarm system provides the evacuation function for that system which would have been provided by alarm sounders (item C of Figure 1 in EN 54-1:1996).
Voice alarm system configurations vary widely to suit different applications.
The most important criteria for defining the system configuration are the applicable design guidelines or code of practice and the emergency procedures for the building, including requirements for audibility and intelligibility.
D.2 Example of a simple voice alarm system
Figure D.1 is a schematic diagram of a simple fire alarm voice alarm system. In this case there is a recorded message which is activated on instruction from the CIE. In such a simple system there may be no emergency microphones or manual controls.
In the example given, the voice alarm system only broadcasts one message at a time and therefore only requires a single audio channel.
D.3 Example of a more complex voice alarm system
Figure D.2 is a schematic diagram of a more complex fire alarm voice alarm system. The system has:
Because this system can play different messages in different fire alarm voice alarm zones and the emergency microphone can also access selected zones; it requires several audio channels.
A complex system may have manual controls for activating messages on different fire alarm voice alarm zones.
D.4 Use of voice alarm for non-fire emergency purposes
A fire alarm voice alarm system may also be used for non-fire alarm purposes as follows:
— for bomb alert messages, in which case the emergency procedures will be different than for a fire alarm;
— for general public address announcements and background music.
In an alarm situation it is normal to prevent the system from being used for non-alarm purposes.
Non-alarm requirements may affect the design significantly. For instance, the sub-division of a voice alarm zone into many paging zones may add significantly to the complexity of the monitoring of the system.
NOTE 1 The VACIE and CIE may be housed in the same cabinet and share common functions (see Annex F). NOTE 2 The VACIE and the CIE may derive their power from the same power supply (item 12).
NOTE 3 The end-of-line device is an example to fulfill the requirement of this standard to monitor the loudspeaker wiring. Other solutions not using an end-of-line device are acceptable.
1 CIE (to EN 54-2)
2 VACIE
3 fire alarm interface
4 emergency microphone(s) and control
5 operational microphone(s) and control
6 indicators
9 message generation
10 amplification
11 voice alarm zone outputs
12 fire alarm device outputs
13 voice alarm zones
14 end-of-line device
15 fire alarm devices
16 power supply equipment
7 manual controls
8 processing, prioritizing and signal routing

EN 54-16 Fire detection and fire alarm systems – Part 16: Voice alarm control and indicating equipment

Leave a Reply

Your email address will not be published. Required fields are marked *

Scroll to top