EN 54-11 Fire detection and fire alarm systems — Part 11: Manual call points

1 Scope
This European Standard specifies the requirements and methods of test for manual call points in fire detection and fire alarm systems in and around buildings. It takes into account indoor and outdoor conditions, the appearance and operation of the manual call points for type A “direct operation” and type B “indirect operation” and covers those which are simple mechanical switches, those which are fitted with simple electronic components (e.g. resistors, diodes) and those which contain active electronic components and which work with the control panels for signalling and identifying, for example, an address or location.
This European Standard does not cover manual call points for special applications, for example manual call points that are intrinsically safe or for use in hazardous conditions, if such applications require additional or other requirements or tests than those given in this standard.

2 Normative references
This European Standard incorporates, by dated or undated reference, provisions from other publications. These normative references are cited at the appropriate places in the text and the publications are listed hereafter. For dated references, subsequent amendments to or revisions of any of these publications apply to this European Standard only when incorporated in it by amendment or revision. For undated references the latest edition of the publication referred to applies (including amendments).

3 Terms and definitions
For the purposes of this European Standard, the terms and definitions given in EN 54-1:1996 apply together with the following.
3.1
alarm condition
the condition of the manual call point after the operating element has been activated
3.2
frangible element
a component which is glass or has the appearance of glass and which after receiving a blow or pressure as instructed, is physically broken or is visibly displaced by change of position and remains in that condition until replaced or reset
NOTE The frangible element is intended to give protection against unintentional operation and to be a deterrent against misuse. The visible displacement of the frangible element is accepted as apparent breaking.
3.2.1
non-resettable frangible element
a frangible element that needs to be replaced after the activation of the manual call point, in order for the manual call point to be able to return to the normal condition
3.2.2
resettable frangible element
a frangible element that can be returned to its original position without replacement, in order for the manual call point to be able to return to the normal condition
3.3
front face
ISO 3864
the area within the outline of the front view of the manual call point excluding the area of the operating face NOTE SEE FIGURES 1 AND 2, ITEM 1.
3.4
manual call point
a component of a fire detection and fire alarm system which is used for the manual initiation of an alarm [EN 54-1:1996]
Manual call points are divided into two types depending on the method of operation:
3.4.1
type A: direct operation
a manual call point in which the change to the alarm condition is automatic (i.e. without the need for further manual action) when the frangible element is broken or displaced
3.4.2
type B: indirect operation
a manual call point in which the change to the alarm condition requires a separate manual operation of the operating element by the user after the frangible element is broken or displaced
3.5
normal condition
the condition in which the frangible element is undamaged and the manual call point is operating without giving an alarm or fault signal
3.6
operating element
mechanical and electrical switching element; the part of the manual call point which initiates the alarm signal when operated
3.7
operating face
that area of the manual call point which may be the visible part of the frangible element or the visible area behind it
NOTE See Figures 1 and 2, item 2.
3.8
special tool
a device not normally carried by the public (e.g. a key), normally provided by the manufacturer and which is used for replacing or resetting the frangible element
NOTE It is intended to deter unauthorized access to the manual call point, while being available on site either at a defined location or from a “responsible person” familiar with and having knowledge of the system.
4 Requirements
4.1 Compliance
In order to comply with this standard the manual call point shall meet the requirements of this clause which shall be verified by visual inspection or engineering assessment, shall be tested as described in clause 5 and shall meet the requirements of the tests.
4.2 Marking and data 4.2.1 Marking
Each manual call point shall be permanently marked with the following information:
Where any marking on the manual call point uses symbols or abbreviations not in common use, then these shall be explained in the data supplied with the device.
The marking shall be visible during installation of the manual call point and shall be accessible during maintenance.
The markings shall not be placed on screws or other easily removable parts.
4.2.2 Data
Manual call points shall either be supplied with sufficient technical, installation and maintenance data to enable their correct installation and operation or, if all of these data are not supplied with each manual call point, reference to the appropriate data sheet shall be given on or with each manual call point.
To enable correct operation of the manual call points, these data shall describe the requirements for the correct processing of the signals from the manual call point. This may be in the form of a full technical specification of these signals, a reference to the appropriate signalling protocol or a reference to suitable types of control and indicating equipment, etc.
NOTE Additional information may be required by organizations certifying that manual call points produced by a manufacturer conform to the requirements of this standard.
4.3 Frangible element
4.3.1 Normal condition
The normal condition shall be easily recognizable by the appearance of the operating face as detailed in 4.7. The frangible element shall be flat and shall not be broken, deformed or displaced.
4.3.2 Alarm condition
Transfer from the normal condition to the alarm condition shall be achieved by the following and shall be easily recognizable by the change in the appearance of the operating face:
In addition, for type B manual call points, it shall be possible to see that the operating element is in the activated position and it shall not be possible to activate the operating element without breaking or displacing the frangible element [see 4.3.2 b)] or without the use of a special tool (see 4.6).
4.4 Indicators for alarm condition
The alarm condition shall be indicated by:
a) for type A: the condition of the frangible element as specified in 4.3;
b) for type B: the frangible element as described in 4.3 together with an identifiable activated position of the operating element.
The alarm condition may be additionally indicated visually by other means, for example using lamps or light-emitting diodes (LEDs).
If an additional visual indicator is provided, it shall be positioned within the operating face or within the front face of the manual call point. The visual indicator shall be red, shall identify the manual call point which released an alarm, until the alarm condition is reset, and shall be visible from a distance of 2 m directly in front of the manual call point in an ambient light intensity up to 500 lx. Where other conditions of the manual call point may be visually indicated, they shall be clearly distinguishable from the alarm indication, except when the manual call point is switched into a service mode.
4.5 Reset facility
It shall only be possible to reset the manual call point after operation by means of a special tool as follows:
In addition, for type B manual call points, it shall only be possible to return the operating element to its normal condition by means of a special tool.
4.6 Test facility
The manual call point shall be equipped with a facility to carry out routine testing when installed. The operation of this test facility shall:
a) simulate the alarm condition by activating the operating element without breaking the frangible element; and
b) allow the manual call point to be reset without breaking the frangible element. The operation of the test facility shall only be possible using a special tool.
4.7 Construction and design
4.7.1 Safety aspects
When operating the frangible element, injury to the operator shall not occur.
For type B manual call points the actuation force of the operating element shall meet the requirements of EN 894-3:2000.
Corners and edges of the manual call points shall be rounded to reduce the possibility of injury, but the radius of curvature shall not exceed 0,05 A (see Table 1).
4.7.2 Shape, dimensions and colours 4.7.2.1 Shape
The front face of the manual call point shall be approximately square in accordance with Table 1.
The operating face shall either be square (see Figure 1) or rectangular (see Figure 2). The operating face in accordance with Table 1, Figure 1 and Figure 2:
The operating face shall be level with or recessed into the front face; it shall not project beyond the front face. 4.7.2.2 Dimensions
The dimensions of the front face and of the operating face shall be within the limits shown in Figure 1, Figure 2 and Table 1. A tolerance of ±5 % may be applied where not otherwise specified.
The manual call point shall be designed so that it is capable of being mounted, in accordance with the manufacturer’s instructions, with the front face at least 15 mm proud of the surrounding surface.

4.7.2.3 Colours
The colour of the visible surface area of the manual call point when mounted in accordance with 5.1.3 shall be red, except for:
The colour of the operating face other than symbols and lettering specified in 4.7.3.3 shall be white. The colour of the visible part of the operating element (type B manual call point) shall be black. NOTE SUITABLE RED, WHITE AND BLACK COLOURS ARE SPECIFIED IN ISO 3864.
4.7.3 Symbols and lettering
4.7.3.1 General
The manual call point shall be marked, with the appropriate symbols shown in Figure 3, as specified in
4.7.3.2 and 4.7.3.3. Examples of the arrangement of symbols on type A and type B manual call points are given in Figures 4 and 5 respectively.
4.7.3.2 Symbols and lettering on the front face
4.7.3.2.1 On the front face above the operating face and central to the vertical centre line shall be the symbol in accordance with Figure 3 a). This symbol may be supplemented with the word “FIRE” or equivalent words in the national language. This combination shall be on the front face and above the operating face and central to the vertical centre line. The height of the symbol shall be at least 0,15 A and the height of the lettering shall not exceed the height of the symbol. The lettering shall be in accordance with ISO 3098-0:1997, “lettering type B, vertical (V)”. Symbols and lettering shall be white in accordance with ISO 3864:1984.
4.7.3.2.2 Markings other than specified in 4.7.3.2.1 (such as company logo or contact address) shall be restricted to the area of the front face below the horizontal centre line of the operating face. The total area for this marking other than red shall not be greater than 5 % of the area of the front face.
4.7.3.3 Symbols and lettering on the operating face
4.7.3.3.1 The operating face of type A manual call points shall be marked with the symbol in accordance with Figures 3 c). The operating face of type B manual call points shall be marked with the symbols in accordance with Figures 3 b) and 3 d). The symbol in accordance with Figure 3 b) shall point to the operating element and shall remain clearly visible when the frangible element is broken or displaced. These symbols may be supplemented by appropriate words for instruction. Where supplementary wording is used, this shall indicate position and/or operating action (e.g. “PRESS HERE”).
These symbols and lettering for any supplementary instructions shall be black with the black area not exceeding 10 % of the area of the operating face.
4.7.3.3.2 Markings other than specified in 4.7.3.3.1 (such as company logo or contact address) shall be restricted to the upper and/or the lower 25 % of the area of the operating face and shall not interfere with the symbols. The total area for this marking other than white shall not be greater than 5 % of the area of the operating face.


4.7.4 Protection against accidental operation
In addition to the use of the frangible element other means of protection may be used, e.g. a transparent flap.
Where used, the protection shall be easily and immediately removable and shall have clear instructions for its removal in order to operate the manual call point.
With the protection in place, the appearance of the manual call point, the instructions for its operation and the state of the manual call point in the normal and alarm condition shall be clearly visible.
4.7.5 Environment category
The environment category (i.e. indoor or outdoor use, special environmental conditions) of the manual call point shall be specified by the manufacturer.
The manual call point shall be tested in accordance with the specified environmental category as given in the test schedule in Table 2.
4.8 Additional requirements for software controlled manual call points
4.8.1 General
For manual call points which rely on software control in order to fulfil the requirements of this standard, the requirements of 4.8.2, 4.8.3 and 4.8.4 shall be met.
4.8.2 Software documentation
4.8.2.1 The manufacturer shall submit documentation which gives an overview of the software design. This documentation shall be in sufficient detail for the design to be inspected for compliance with this standard and shall include at least the following:
a) A functional description of the main program flow (e.g. as a flow diagram or structogram) including:
1) a brief description of the modules and the functions that they perform;
2) the way in which the modules interact;
3) the overall hierarchy of the program;
4) the way in which the software interacts with the hardware of the manual call point;
5) the way in which the modules are called, including any interrupt processing.
b) A description of which areas of memory are used for the various purposes (e.g. the program, site specific data and running data).
c) A designation, by which the software and its version can be uniquely identified.
4.8.2.2 The manufacturer shall have available detailed design documentation, which only needs to be provided if required by the testing authority. It shall comprise at least the following:
a) An overview of the whole system configuration, including all software and hardware components.
b) A description of each module of the program, containing at least:
1) the name of the module;
2) description of the tasks performed;
3) description of the interfaces, including the type of data transfer, the valid data range and the checking for valid data.
c) Full source code listings, as hard copy or in machine-readable form (e.g. ASCII-code), including all global and local variables, constants and labels used, and sufficient comment for the program flow to be recognized.
d) Details of any software tools used in the design and implementation phase (e.g. CASE-tools, compilers).
4.8.3 Software design
In order to ensure the reliability of the manual call point, the following requirements for software design shall apply:
a) the software shall have a modular structure;
b) the design of the interfaces for manually and automatically generated data shall not permit invalid data to cause error in the program operation;
c) the software shall be designed to avoid the occurrence of deadlock of the programme flow.
4.8.4 The storage of programs and data
The program necessary to comply with this standard and any preset data, such as manufacturer’s settings, shall be held in non-volatile memory. Writing to areas of memory containing this program and data shall only be possible by the use of some special tool or code and shall not be possible during normal operation of the manual call point.
Site-specific data shall be held in memory which will retain data for at least two weeks without external power to the manual call point, unless provision is made for the automatic renewal of such data, following loss of power, within 1 h of power being restored.
5 Tests
5.1 General
5.1.1 Atmospheric conditions for tests
Unless otherwise stated in a test procedure, the testing shall be carried out after the test specimen has been allowed to stabilize in the standard atmospheric conditions for testing, as described in IEC 60068-1:1988, as follows:
5.1.2 Operating conditions for tests
If a test method requires a specimen to be operational, then the specimen shall be connected to a suitable supply and monitoring equipment with characteristics as required by the manufacturer’s data. Unless otherwise specified in the test method, the supply parameters applied to the specimen shall be set within the manufacturer’s specified range(s) and shall remain substantially constant throughout the tests. The value chosen for each parameter shall normally be the nominal value, or the mean of the specified range. If a test procedure requires a specimen to be monitored to detect any alarm or fault signals, then connections shall be made to any necessary ancillary devices (e.g. through wiring to an end-of-line device for conventional manual call points) to allow a fault signal to be recognized.
NOTE The details of the supply and monitoring equipment and the alarm criteria used should be given in the test report.
5.1.3 Mounting arrangements
The specimen shall be mounted by its normal means of attachment in accordance with the manufacturer’s instructions. If these instructions describe more than one method of mounting, then the method considered to be most unfavourable shall be chosen for each test.
5.1.4 Tolerances
Unless otherwise stated, the tolerances for the environmental test parameters shall be as given in the basic reference standards for the test (e.g. the relevant part of IEC 60068).
If a specific tolerance or deviation limit is not specified in a requirement or test procedure, then a deviation limit of ±5 % shall be applied.
5.1.5 Measurement of response time
Where the release of an alarm signal in the following tests is required, the alarm signal shall be indicated at the supply and monitoring equipment (see 5.1.2) within a response time of 10 s after the operating element has been activated.
This response time shall be measured and reported.
5.1.7 Test schedule
The specimens shall be randomly numbered:
a) 1 to 8, if they are for indoor use and are simple switches or contain simple electronic components;
b) 1 to 13, if they are for indoor use and contain active electronic components;
c) 1 to 8 and 14, if they are for outdoor use and are simple switches or contain simple electronic components;
d) 1 to 14, if they are for outdoor use and contain active electronic components.
Any change in the number and numbering of specimens, e.g. in line with Table 2, shall be recorded in the test report accordingly.
All specimens shall be initially tested in accordance with the test facility test of 5.4 and then be tested in accordance with 5.2 Operational performance test
5.2.1 Object
To demonstrate that the manual call point is able to withstand small forces to the frangible element without operation, is able to operate when an appropriate force is applied to the frangible element by the user and that its reset and test facilities are not impaired.
5.2.2 Test procedure 5.2.2.1 Test for non-operation
5.2.2.1.1 State of the specimen during test
The specimen shall be mounted in accordance with 5.1.3 and connected to a suitable supply and monitoring equipment as described in 5.1.2.
5.2.2.1.2 Initial state
At the start of the test the specimen shall be in its normal condition.
5.2.2.1.3 Conditioning
The frangible element shall be subjected to a horizontal force increasing at a rate not exceeding 5 N s-1 until it reaches (22,5 ± 2,5) N. This force is maintained for 5 s then released at a rate not exceeding 5 N s-1. The position where this force shall be subjected is the centre point between the arrows, see Figures 3 c) and 3 d).
An example of a suitable test apparatus is shown in annex B.
5.2.2.1.4 Measurements during testing
The specimen shall be monitored during the test period to detect any alarm or fault signals.
5.2.2.1.5 Final measurements
a) After the force has been released, the frangible element shall be examined.
b) The specimen shall then be tested as described in the test facility test of 5.4. 5.2.2.2 Test for operation
5.2.2.2.1 Conditioning
The frangible element shall be subjected to a horizontal impact within 5 mm of the centre point between the arrows, see Figures 3 c) and 3 d).
The impact shall be produced by using the test apparatus in accordance with annex A. The ball shall strike the specimen once only.
For type B manual call points, the operating element shall then be manually operated.
5.2.2.2.2 State of the specimen during test
The specimen shall be mounted on the test apparatus (see annex A) in its normal operating position in accordance with 5.1.3 and connected to a suitable supply and monitoring equipment as described in 5.1.2.
5.2.2.2.3 Initial state
At the start of the test the specimen shall be in its normal condition.
5.2.2.2.4 Resetting
After operation, the specimen shall be reset to its normal condition by using the reset facility of 4.5.
5.2.2.2.5 Measurements during testing
The specimen shall be monitored during the test and resetting period to detect any alarm or fault signals. 5.2.3 Test requirements
The specimen shall satisfy the following requirements:
a) in the test of 5.2.2.1 the frangible element shall not transfer into the alarm condition and no alarm or fault signal shall be given, except as required in the test of 5.2.2.1.5 b). In the test of 5.2.2.1.5 b) the specimen shall comply with the requirements of 5.4.3;
b) for type A – in the test of 5.2.2.2 the frangible element shall transfer into the alarm condition and an alarm signal shall be given in accordance with 5.1.5. After the specimen has been reset by use of the reset facility of 4.5 there shall be no alarm or fault signal;
c) for type B – in the test of 5.2.2.2 the frangible element shall transfer into the alarm condition and an alarm signal shall be given in accordance with 5.1.5 after activation of the operating element. After the specimen has been reset by use of the reset facility of 4.5 there shall be no alarm or fault signal.
5.3 Function test
5.3.1 Object
To demonstrate the ability of the electrical parts of the manual call point to function correctly.
5.3.2 Test procedure
The test may be performed as described in 5.2.2.2 (test for operation) or using the test facility according to 4.6 or some other means which activate the operating element.
NOTE This can be parts or combinations of the operational performance test and the test facility test with suitable modifications to help the test laboratories to carry out the environmental tests.
For the dry heat (operational) test according to 5.7 and cold (operational) test according to 5.9, the function tests during conditioning [see 5.7.2.4 b) and 5.9.2.4 b) respectively] shall use a procedure which does not result in breakage of the frangible element.
5.3.3 Test requirements
An alarm signal shall be given in accordance with 5.1.5 when the operating element has been activated.
5.4 Test facility test (operational)
5.4.1 Object
To demonstrate the ability of the test facility (see 4.6) of the manual call point to function correctly.
5.4.2 Test procedure
5.4.2.1 General
The test shall be carried out in accordance with the manufacturer’s instructions for routine testing by using the test facility of 4.6.
5.4.2.2 State of the specimen during test
The specimen shall be mounted in accordance with 5.1.3 and connected to a suitable supply and monitoring equipment as described in 5.1.2.
5.4.2.3 Measurements during testing
5.5 Reliability test (endurance)
5.5.1 Object
To demonstrate the reliability of the operating element.
5.5.2 Test procedure
5.5.2.1 Test apparatus
A suitable method of activating and resetting the operating element shall be used, which for type A simulates the frangible element’s alarm condition followed by the resetting to its normal condition and for type B activates and resets the operating element with the frangible element removed.
NOTE If suitable, the test facility of 4.6 can be used for this test.
5.5.2.2 State of the specimen during conditioning
The specimen shall be mounted in accordance with 5.1.3 and connected to a suitable supply and monitoring equipment as described in 5.1.2. The supply parameters shall be adjusted within the manufacturer’s specifications for conditions most likely to cause failure.
5.5.2.3 Conditioning
The following severity shall be applied:
5.5.3 Test requirements
The following requirements shall be satisfied:
a) There shall be no visible damage to the specimen likely to impair its operation.
b) In the test of 5.5.2.4 b) the specimen shall comply with the requirements of 5.2.3.
5.6 Variation of supply parameters
5.6.1 Objects
To demonstrate that within the manufacturer’s specified upper and lower limits of the supply parameters, the ability of the manual call point to signal an alarm is not unduly dependent on these parameters for correct operation.
5.6.2 Test procedure
5.6.2.1 State of the specimen during conditioning
The specimen shall be connected to a suitable supply and monitoring equipment as described in 5.1.2.
5.6.2.2 Conditioning
The supply parameters shall be set within the manufacturer’s specifications to the upper limit for a period of 5 min and then to the lower limit for a period of 5 min. The values of the parameters shall be reported.
5.6.2.3 Measurements during conditioning
a) The specimen shall be monitored during the conditioning period to detect any alarm or fault signals.
b) At the end of each conditioning period the function test of 5.3 shall be carried out at the upper and lower limits respectively.
c) The specimen shall be reset after each function test.
d) 5.6.3 Test requirements
The following requirements shall be satisfied:
a) No alarm or fault signals shall be given during the conditioning period, except as required in the tests of 5.6.2.3 b).
b) In the test of 5.6.2.3 b) the specimen shall comply with the requirements of 5.3.3.
c) After the specimen has been reset there shall be no alarm or fault signal.
5.7 Dry heat (operational)
5.7.1 Object
To demonstrate the ability of the manual call point to function correctly at high ambient temperatures, which may occur for short periods in the anticipated service environment.
5.7.2 Test procedure 5.7.2.1 Reference
The test apparatus and the test procedure shall be as described in IEC 60068-2-2:1974, IEC 60068-2-2/A1:1993 and IEC 60068-2-2/A2:1994, test Bb.
5.77.2.2 State of the specimen during conditioning
The specimen shall be mounted in accordance with 5.1.3 and connected to a suitable supply and monitoring equipment as described in 5.1.2. The supply parameters shall be adjusted within the manufacturer’s specifications for conditions most likely to cause failure.
5
5.7.2.5 Final measurements
After a recovery period of at least 1 h at standard atmospheric conditions in accordance with 5.1.1, the specimen shall be reset and then be tested as described in the operational performance test of 5.2.
The dry heat operational and endurance tests may be combined such that the specimen for outdoor use is subjected to the operational test conditioning followed (after resetting) by the endurance test conditioning. Only one final measurement shall be made.
5.7.3 Test requirements
The following requirements shall be satisfied:
a) No alarm or fault signal shall be given during the conditioning period, except as required in the test of 5.7.2.4.
b) In the test of 5.7.2.4 b) the specimen shall comply with the requirements of 5.3.3.
c) In the test of 5.7.2.5 the specimen shall comply with the requirements of 5.2.3.
5.8 Dry heat (endurance)
5.8.1 Object
To demonstrate the ability of the manual call point to withstand long term ageing effects.
5.8.2 Test procedure
5.8.2.1 Reference
The test apparatus and the test procedure shall be as described in IEC 60068-2-2:1974, IEC 60068-2-2/A1:1993 and IEC 60068-2-2/A2:1994, test Bb.
5.8.2.2 State of the specimen during conditioning
The specimen shall be mounted in accordance with 5.1.3 and not supplied with power during the conditioning.
5.8.2.4 Final measurements
After a recovery period of at least 1 h at standard atmospheric conditions in accordance with 5.1.1, the specimen shall be tested as described in the reliability test of 5.5.
5.8.3 Test requirements
The following requirements shall be satisfied:
a) No fault signal attributable to the endurance conditioning shall be given on connection of the specimen.
b) In the test of 5.8.2.4 the specimen shall comply with the requirements of 5.5.3.
5.9 Cold (operational)
5.9.1 Object
To demonstrate the ability of the manual call point to function correctly at low ambient temperatures appropriate to the anticipated service environment.
5.9.2 Test procedure
5.9.2.1 Reference
The test apparatus and the test procedure shall be as described in IEC 60068-2-1:1990, IEC 60068-2-1/A1:1993 and IEC 60068-2-1/A2:1994 , test Ab.
5.9.2.2 State of the specimen during conditioning
The specimen shall be mounted in accordance with 5.1.3 and connected to a suitable supply and monitoring equipment as described in 5.1.2. The supply parameters shall be adjusted within the manufacturer’s specifications for conditions most likely to cause failure.
5.9.2.3 Measurements during conditioning
a) The specimen shall be monitored during the conditioning period to detect any alarm or fault signals.
b) During the last half hour of the conditioning period, the function test of 5.3 shall be carried out.
5.9.2.4 Final measurements
After a recovery period of at least 1 h at standard atmospheric conditions in accordance with 5.1.1, the specimen shall be reset and then be tested as described in the operational performance test of 5.2.
5.9.3 Test requirements
The following requirements shall be satisfied:
a) No alarm or fault signal shall be given during the conditioning period, except as required in the test of 5.9.2.4.
b) In the test of 5.9.2.4 b) the specimen shall comply with the requirements of 5.3.3.
c) In the test of 5.9.2.5 the specimen shall comply with the requirements of 5.2.3.
5.10 Damp heat, cyclic (operational)
5.10.1 Object
To demonstrate the ability of the manual call point to function correctly at high relative humidity, where condensation occurs on the manual call point.
5.10.2 Test procedure
5.10.2.1 Reference
The test apparatus and the test procedure shall be as described in IEC 60068-2-30:1980 and IEC 60068-2-30/A1:1985, test Db, using the Variant 1 test cycle and controlled recovery conditions.
5.10.2.2 State of the specimen during conditioning
The specimen shall be mounted in accordance with 5.1.3 and connected to a suitable supply and monitoring equipment as described in 5.1.2. The supply parameters shall be adjusted within the manufacturer’s specifications for conditions most likely to cause failure.
5.10.2.3 Measurements during conditioning
The specimen shall be monitored during the conditioning period to detect any alarm or fault signals.
5.10.2.4 Final measurements
After the recovery period specified in IEC 60068-2-30:1980 and IEC 60068-2-30/A1:1985, the specimen shall be tested as described in the operational performance test of 5.2.
The damp heat, cyclic operational and endurance tests may be combined such that the specimen for outdoor use is subjected to the operational test conditioning followed by the endurance test conditioning. Only one final measurement shall be made.
5.10.3 Test requirements
The following requirements shall be satisfied:
a) No alarm or fault signals shall be given during the conditioning period.
b) In the test of 5.10.2.5 the specimen shall comply with the requirements of 5.2.3.
5.11 Damp heat, cyclic (endurance)
5.11.1 Object
To demonstrate the ability of the manual call point to withstand the longer term effects of high humidity and condensation.
5.11.2 Test procedure
5.11.2.1 Reference
The test apparatus and the test procedure shall be as described in IEC 60068-2-30:1980 and IEC 60068-2-30/ A1:1985, test Db, using the Variant 1 test cycle and controlled recovery conditions.
5.11.2.2 State of the specimen during conditioning
The specimen shall be mounted in accordance with 5.1.3 and not supplied with power during the conditioning.
5.11.2.3 Conditioning
The appropriate test conditions in Table 7 shall be applied.
5.12.2 Test procedure
5.12.2.1 Reference
The test apparatus and the test procedure shall be as described in IEC 60068-2-56:1988, test Cb. If this is impracticable, the test apparatus and the test procedure may be used as described in IEC 60068-2-3:1969, test Ca.
5.12.2.2 State of the specimen during conditioning
The specimen shall be mounted in accordance with 5.1.3 and not supplied with power during the conditioning.
5.12.2.3 Conditioning
After a recovery period of at least 1 h at standard atmospheric conditions in accordance with 5.1.1, the specimen shall be tested as described in the reliability test of 5.5.
5.12.3 Test requirements
The following requirements shall be satisfied:
a) No fault signal attributable to the endurance conditioning shall be given on connection of the specimen.
b) In the test of 5.12.2.4 the specimen shall comply with the requirements of 5.5.3. 5.13 SO2 corrosion (endurance)
5.13.1 Object
To demonstrate the ability of the manual call point to withstand the corrosive effects of sulfur dioxide as an atmospheric pollutant.
5.13.2 Test procedure
5.13.2.1 Reference
The test apparatus and the test procedure shall be as described in IEC 60068-2-42:1982, test Kc, except for the relative humidity of the test atmosphere, which shall be (93 ± 3) % instead of (75 ± 5) %.
5.13.2.2 State of the specimen during conditioning
The specimen shall be mounted in accordance with 5.1.3. It shall not be supplied with power, but shall have untinned copper wires of the appropriate diameter connected to sufficient terminals, to allow the final measurements to be made, without making further connections to the specimen.
5.14.2.1 Reference
The test apparatus and the test procedure shall be as described in IEC 60068-2-27:1987, test Ea, for a half sine wave pulse but with the peak acceleration related to the specimen mass as indicated in Table 10.
5.14.2.2 State of the specimen during conditioning
The specimen shall be mounted in accordance with 5.1.3 to a rigid fixture and connected to a suitable supply and monitoring equipment as described in 5.1.2.
5.14.2.3 Conditioning
For specimens with a mass M< 4,75 kg the test conditions in Table 10 shall be applied. No test is applied to specimens with a mass M > 4,75 kg.
5.14.2.4 Measurements during conditioning
The specimen shall be monitored during the conditioning period and for a further 2 min to detect any alarm or fault signals.
5.14.2.5 Final measurements
After the conditioning, the specimen shall be tested as described in the operational performance test of 5.2.
5.14.3 Test requirements
The following requirements shall be satisfied:
a) No alarm or fault signals shall be given during the conditioning period or the additional 2 min.
b) In the test of 5.14.2.5 the specimen shall comply with the requirements of 5.2.3. 5.15 Impact (operational)
5.15.1 Object
To demonstrate the immunity of the manual call point to mechanical impacts upon its surface, which it may sustain in the normal service environment, and which it can reasonably be expected to withstand.
5.15.2 Test procedure
5.15.2.1 Apparatus
The test apparatus shall consist of a swinging hammer incorporating a rectangular-section aluminium alloy head (aluminium alloy AlCu4SiMg complying with ISO 209-1:1989, solution treated and precipitation treated condition) with the plane impact face chamfered to an angle of 60° to the horizontal, when in the striking position (i.e. when the hammer shaft is vertical). The hammerhead shall be (50 ± 2,5) mm high, (76 ± 3,8) mm wide and (80 ± 4) mm long at mid height as shown in Figure C.1. A suitable apparatus is described in annex C.
The hard wood mounting board shall have width and height dimensions of not less than 20 mm greater than the dimensions A and B in Figures 1 and 2 and a minimum thickness of 40 mm and a minimum mass of not less than 5 times that of the manual call point. It shall be fixed to the rigid frame to allow the manual call point to be located in the positions shown in Figure C.2 and Figure C.3.
5.15.2.2 State of the specimen during conditioning
The specimen shall be mounted to the test apparatus in accordance with 5.1.3 and connected to a suitable supply and monitoring equipment as described in 5.1.2. It shall be positioned so that it is struck by the middle of the lower half of the impact face when the hammer is in the vertical position (i.e. when the hammerhead is moving horizontally). A first impact shall be applied to the specimen from the side to the left or right lower side edge where the hammerhead is moving (in parallel) not more than 5 mm apart from the specimen’s mounting board (see Figure C.2). A second impact shall be applied from the front to the central part of the lower edge of the front face (see Figure C.3).
5.15.2.3 Conditioning
The test conditions in Table 11 shall be applied.
The specimen shall be monitored during the conditioning period and for a further 2 min to detect any alarm or fault signals.
5.15.2.4 Final measurements
After the conditioning, the specimen shall be tested as described in the operational performance test of 5.2.
5.15.3 Test requirements
The following requirements shall be satisfied:
a) No alarm or fault signals shall be given during the conditioning period or the additional 2 min.
b) In the test of 5.15.2.5 the specimen shall comply with the requirements of 5.2.3. 5.16 Vibration, sinusoidal (operational)
5.16.1 Object
To demonstrate the immunity of the manual call point to vibration at levels considered appropriate to the normal service environment.
5.16.2 Test procedure
5.16.2.1 Reference
The test apparatus and the test procedure shall be as described in IEC 60068-2-6:1995, test Fc.
5.16.2.2 State of the specimen during conditioning
The specimen shall be mounted to the test apparatus in accordance with 5.1.3 and connected to a suitable supply and monitoring equipment as described in 5.1.2
The vibration shall be applied in each of three mutually perpendicular axes, in turn. The specimen shall be mounted so that one of the three axes is perpendicular to its normal mounting plane.
5.16.2.3 Conditioning
5.16.2.4 Measurements during conditioning
The specimen shall be monitored during the conditioning period to detect any alarm or fault signals.
5.16.2.5 Final measurements
After the conditioning, the specimen shall be tested as described in the operational performance test of 5.2.
The vibration operational and endurance tests may be combined such that the specimen is subjected to the operational test conditioning followed by the endurance test conditioning in one axis before changing to the next axis. Only one final measurement shall be made.
5.16.3 Test requirements
The following requirements shall be satisfied:
a) No alarm or fault signals shall be given during the conditioning period.
b) In the test of 5.16.2.5 the specimen shall comply with the requirements of 5.2.3. 5.17 Vibration, sinusoidal (endurance)
5.17.1 Object
To demonstrate the ability of the manual call point to withstand the long term effects of vibration at levels appropriate to the normal service environment.
5.17.2 Test Procedure
5.17.2.1 Reference
The test apparatus and the test procedure shall be as described in IEC 60068-2-6:1995, test Fc.
5.17.2.2 State of the specimen during conditioning
The specimen shall be mounted to the test apparatus in accordance with 5.1.3 and not supplied with power during the conditioning.
The vibration shall be applied in each of three mutually perpendicular axes, in turn. The specimen shall be mounted so that one of the three axes is perpendicular to its normal mounting plane.
After the conditioning, the specimen shall be tested as described in the operational performance test of 5.2.
5.17.3 Test requirements
The following requirements shall be satisfied:
a) No fault signal attributable to the endurance conditioning shall be given on connection of the specimen.
b) In the test of 5.17.2.4 the specimen shall comply with the requirements of 5.2.3. 5.18 Electromagnetic compatibility (EMC) (operational)
5.18.1 Object
To demonstrate the capability of the manual call point to comply with the EMC immunity requirements in its normal service environment.
5.18.2 Test procedure
5.18.2.1 Reference
The test apparatus and the test procedures shall be as described in EN 50130-4:1995. The following tests shall be applied:
a) Electrostatic discharge.
b) Radiated electromagnetic fields.
c) Conducted disturbances induced by electromagnetic fields.
d) Fast transient burst.
e) Slow high energy voltage surges.
5.18.2.2 State of the specimen during conditioning
The specimen shall be mounted in accordance with 5.1.3 and connected to a suitable supply and monitoring equipment as described in 5.1.2
5.18.2.3 Conditioning
The test conditions specified in EN 50130-4:1995 for the tests listed in 5.18.2.1 shall be applied.
5.18.2.4 Measurement during conditioning
The specimen shall be monitored during the conditioning period to detect any alarm or fault signals.
5.18.2.5 Final measurements
After the conditioning, period, the function test of 5.3 shall be carried out. The specimen shall be reset after the function test.
5.18.3 Test requirements
The following requirements shall be satisfied:
a) No alarm or fault signals shall be given during the conditioning period.
b) In the test of 5.18.2.5 the specimen shall comply with the requirements of 5.3.3.
c) After the specimen has been reset there shall be no alarm or fault signal.
5.19 Enclosure protection
5.19.1 Object
To demonstrate that the manual call point is adequately protected against the ingress of water.
5.19.2 Test procedure
5.19.2.1 Reference
The test apparatus and the test procedure shall be as described in IEC 60068-2-18:1989 and IEC 60068-2-18/A1:1993, test Rb2.1.
5.19.2.2 State of the specimen during conditioning
The specimen shall be mounted to the apparatus in accordance with 5.1.3 and connected to a suitable supply and monitoring equipment as described in 5.1.2.
5.19.2.3 Conditioning
The appropriate test conditions in Table 14 shall be applied.
The specimen shall be monitored during the conditioning period to detect any alarm or fault signals.
5.19.2.4 Final measurements
After the conditioning, the specimen shall be tested as described in the operational performance test of 5.2.

EN 54-11 Fire detection and fire alarm systems — Part 11: Manual call points

Leave a Reply

Your email address will not be published. Required fields are marked *

Scroll to top